4 Digits digital indicator
Easy to use front panel keypad
5A/60mV, CT20/30 current transformer/60mV or 1A input
AC, DC, or True RMS measurement feature
Programmable scale range between 5A to 9999A
0-20mA, 4-20mA, 0-10V or 1-5V output selection
Triple isolation between input, output and power
Isolated Modbus RTU communication (optional)
Keylock feature
Rail mounted
Plug-in terminals connection
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | IP 20 According to EN60529 |
Height | Max. 2000m |
Electrical Characteristics | |
Input Type | For ECCC-xV 5A or 60mV For ECCC-CT-xV CT20/30 current transformer or 60mV For ECCC-X1-xV 1A |
Scale | AC and RMS: Input type 5A/60mV: 0...9999A (specified by c.tr.r parameter) For example: If c.tr.r=5, scale is 0...5A Input type CT20/30 or 60mV: If itYP=Ct20, input range is 0...300A (specified by turn parameter) For example: If turn=1, scale is 0...300A itYP=Ct30, input range is 0...120A (specified by tUrn parameter) For example: If turn=1, scale is 0...120A Input type 1A: 0...9999A (specified by c.tr.r parameter) For example: If c.tr.r=1, scale is 0...1A DC: Input type 5A/60mV: -999...9999A (specified by c.t.r.r parameter) For example: If c.tr.r=5, scale is -5...5A Input type CT20/30/60mV : DC Measurement can not be performed by using current transformer If itYP=SHnt, input range is -999..9999A (specified by c.tr.r parameter) For example: If c.tr.r=5, scale is -5...5A Input type 1A : -999...9999A (specified by c.t.r.r parameter) For example: c.tr.r=1 için scale -1...1A |
Sensitivity | 0.002A x c.t.r.r (for example, 0.01A for c.t.r.r=5) |
Accuracy | AC: ±1%(of full scale) (±2% for square wave form) DC: ±1% (of full scale) RMS: ±1% (of full scale) (±2% for square wave form) |
Input Range | Input type 60mV: -60mV...60mV (device may be damaged at 50V and above voltages) Input type 1A: -1A...1A (device may be damaged at 2A and above currents) Input type 5A: -5A...5A (device may be damaged at 10A and above currents) Input type CT20/30 : 0...150mA |
Input Impedance | Input type 60mV: 20kohm Input type 1A: 90mohm Input type 5A: 12mohm Input type CT20/30: 600mohm |
Frequency Range | DC, 20Hz - 70Hz |
Supply | ECCC411-UV: 90-250V AC, 50/60Hz ECCC411-LV: 10-30V DC or 8-24V AC, 50/60Hz |
Power Consumption | Max. 7VA |
Outputs | mA: 0-20mA DC or 4-20mA DC, ±0,5% (load resistance max. 500Ω) V: 0-10V DC or 1-5V DC, max.10mA, ±0,5% (Short circuit protected) |
External Connections | Plug-in terminals |
Housing | |
Mounting Method | TH35 rail mounting |
Dimensions | W25xH97xD115 mm |
Weight | Approx. 150g (after packaging) |