EDT5412A
  • On-Off control

  • Relay output for cooling or heating control

  • Relay output for defrosting or lighting

  • Single NTC probe input

  • Offset value can be adjusted for NTC probe

  • Compressor protection parameters can be adjusted

  • In the case of probe failure, output state can be selected as on-off or periodical running

  • Upper and lower limits of the set point can be adjusted

  • Defrosting duration and interval can be adjusted

  • 6 different warning tones

  • Upper and lower limits of the alarm value can be adjusted depending on the set point value

  • Temperature unit can be selected as °C or °F

  • External alarm can be given by using digital input

  • Parameter can be transferred by using “ENDAKEY” without connecting the device to mains supply

  • Communication feature over RS485 ModBus protocol (optional)

  • With Real Time Clock, energy-saving and defrosting feature and configurable lighting feature(optional)

  • Defrosting can be started by using digital input

  • Manually defrosting or lighting(configurable) feature

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeAccording to EN 60529 Front panel:IP65, Rear panel:IP20
HeightMax. 2000m
Electrical Characteristics
Supply230V AC +%10 -%20 50/60Hz or 10-30V DC / 8-24V AC
Power ConsumptionMax. 5VA
External ConnectionsScrew-terminals
Scale-60.0...150.0 °C
Sensitivity0.1°C (Can be chosen as 0.1ºC or 1ºC)
Accuracy±1 (of full scale)
Time accuracy±%1
Output
Relay8A model: 250V AC, 8A (for resistive load), NO+NC
1/2hp 240V AC (for inductive load)
20A model: 277V AC, 20A (for resistive load), NO
2hp 250V AC (for inductive load)
Defrost/Light Relay Output8A model: 250V AC,8A (for resistive load), NO
1/2hp 240V AC (for inductive load)
Life Expectancy8A model: Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load)
20A model: Mechanical 10.000.000 operations (under no load), Electrical 100.000 operations (20A at 277V AC, resistive load)
Life Expectancy for Defrost/Light Relay Output8A model: Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load)
Control
Control typeSingle set-point and alarm control
Control algorithmOn-Off
HysteresisAdjustable between 1 and 20.0 °C
Housing
Mounting MethodTH35 rail mounting
DimensionsW54xH94xD68mm
WeightApprox. 190g (After packing)
Enclosure materialSelf extinguishing plastics
Please choose your preferred language.