EPC9513
  • 3,5 inches TFT , graphic and 5 digit display

  • Selectable TC, RTD, NTC, R, mA, V or mV inputs

  • Input offset feature

  • 32 point linearization for analog inputs

  • Selectable relay, SSR or analog outputs

  • Selectable, input proportional transmitter output (mA or V)

  • 50ms sampling time

  • PID control

  • PID selftune

  • PID auto-tune

  • Soft-Start feature

  • 24Vdc for sensor supply

  • 16 program and 8 step for profile control

  • Selectable Single Setpoint Mode or Profile Control Mode

  • Digital inputs for profile control

  • In case of sensor failure manually, periodical or auto-periodical control can be selected

  • Security levels for menu and configuration pages

  • RS-485 ModBus protocol communication feature (optional)

  • CE marked according to Europen Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeAccording to EN 60529 Front panel: IP65, Rear panel: IP20
HeightMax. 2000m
Electrical Characteristics
Supply90-250V AC, 50/60Hz
Power Consumption7VA
External ConnectionsPlug-in terminals
ScalePt-100 resistance thermometer -200.0...850.0 °C / -100.0...160.0 °C
Pt30Rh-Pt6Rh (B) thermocouple 200.0...1800.0 °C
NiCr-Con (E) thermocouple -100.0...900.0 °C
Fe-Con (J) thermocouple -100.0...900.0 °C
NiCr-Ni (K) thermocouple -100.0...1300.0 °C
Fe-Con (L) thermocouple -100.0...900.0 °C
NiCrSi-NiSi (N) thermocouple -200.0...1300.0 °C
Pt13Rh-Pt (R) thermocouple 0.0...1700.0 °C
Pt10Rh-Pt (S) thermocouple 0.0...1700.0 °C
Cu-Con (T) thermocouple -250.0...300.0 °C
Cu-Con (U) thermocouple -200.0...400.0 °C
NTC -60.0...150.0 °C
For 0/4 - 20mA, 0 - 150mV, 0/1 - 5V, 0 - 10V, 0 - 550ohm, 0 - 10kohm:
-32768...32767 (decimal point can be adjusted between 1. and 3. digits)
Digital Input5V or 30V pulse , Ri=100kohm (in order to use for profile control process)
Accuracy±%0.1 or ±2 °C (for B type thermocouple)
±%0.1 or ±0.5 °C (for E, J, K, N, T, U type thermocouple, Pt-100 resistance thermometer, NTC probe)
±%0.1 or ±1.5 °C (for L type thermocouple)
±%0.1 or ±1 °C (for R, S type thermocouple)
±%0.1 or ±1 digit (for 0/4 - 20mA, 0/1 - 5V, 0 - 10V)
±%0.1 or ±20μV (for 0 - 150mV)
±%0.2 or ±0.1ohm (for 0 - 550ohm)
±%0.5 or ±10ohm (for 0 - 10kohm)
Line ResistanceFor Thermocouple, Pt-100, NTC, mV, V, ohm Ri > 100kohm
For mA Ri = 50ohm
Output
Control/Alarm 3 OutputRelay: 250V AC, 2A (resistive load), NO+NC
Alarm 1 OutputRelay: 250V AC, 2A ( resistive load), NO+NC
Alarm 2 OutputRelay: 250V AC, 2A ( resistive load), NO
SSR OutputMax. 40mA, 0 - 12V, short-circuit protection
mA Output0 - 20mA or 4 - 20mA max. load resistance is 750ohm
V OutputMax. 30mA, 0 - 10V DC, short-circuit protection
Life ExpectancyMechanical 10.000.000 operations (under no load), Electrical 200.000 operations (2A at 250V AC, resistive load)
Housing
Mounting MethodPanel mounting
DimensionsW96xH96xD81 mm
WeightApprox. 400g (after packaging)
Enclosure MaterialSelf extinguishing plastics