Selectable 0-20mA, 4-20mA, or 0-10V input
Manual input of PID parameters
Soft-Start function
Offset feature for input
0-20mA, 4-20mA, and 0-10V analogue control output
Communication via RS-485 Modbus protocol
CE marked according to European Norms
Environmental Specifications | |
Ambient/Storage Temperature | 0...50 °C / -25...70 °C |
Relative Humidity | 80% relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C |
Protection Degree | According to EN 60529 Front Panel: IP62, Rear Panel: IP20 |
Height | Max. 2000m |
Electrical Specifications | |
Supply | 90-250V AC 50/60Hz; 10-30V DC / 8-24V AC SMPS |
Power Consumption | Max. 5VA |
Connection | Power terminal 2.5mm² socket terminal |
Line Resistance | Maximum 100ohm |
Data Protection | EEPROM (minimum 10 years) |
EMC | EN 61326-1: 2021 |
Outputs | |
mA Output | 0-20mA DC or 4-20mA DC, ±5% (maximum load resistance of 500ohm) |
V Output | 0-10V DC, ±5% (short circuit protection included) |
Sensor Output | 24V DC, maximum 25mA |
Control | |
Control Type | Single set point and alarm control |
Control Method | P, PI, PD, PID (selectable) |
A/D Converter | 12-bit |
Sampling Time | 100ms |
Proportional Band | Adjustable between %0.0 to %100.0. If Pb=%0.0, On-Off control is selected. |
Control Period | Adjustable between 1 to 250 seconds |
Hysteresis | Adjustable between 1 to 50 |
Output Power | The ratio of power at a set point can be adjusted between 0% and 100% |
Housing | |
Housing Type | Fits compressed into panel (according to DIN 43 700) |
Dimensions | W77xH35xD71mm |
Weight | Approximately 215g (packaged) |
Enclosure Materials | Self-extinguishing plastics |