3,5 inches TFT, graphic and 5 digit display
2 sensor inputs selectable as TC, RTD, NTC, R, mA, V or mV
Input offset feature
32 point linearization for analog inputs
Selectable relay, SSR or analog outputs
Selectable input proportional transmitter output (mA or V)
50ms sampling time
PID control
PID selftune
PID auto-tune
Soft-Star feature
24V DC for sensor supply
Security levels for menu and configuration page
Programming with Key Pad and ModBus
RS-485 ModBus protocol communication feature (optional)
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel: IP65, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 90-250V AC 50/60Hz |
Power Consumption | 7VA |
External Connections | Plug-in terminals |
Scale | Pt-100 resistance thermometer -200.0...850.0 °C / -100.0...160.0 °C Pt30Rh-Pt6Rh(B) thermocouple 200.0...1800.0 °C NiCr-Con (E) thermocouple -100.0...900.0 °C Fe-Con (J) thermocouple -100.0...900.0 °C NiCr-Ni (K) thermocouple -100.0...1300.0 °C Fe-Con (L) thermocouple -100.0...900.0 °C NiCrSi-NiSi (N) thermocouple -200.0...1300.0 °C Pt13Rh-Pt (R) thermocouple 0.0...1700.0 °C Pt10Rh-Pt (S) thermocouple 0.0...1700.0 °C Cu-Con (T) thermocouple -250.0...300.0 °C Cu-Con (U) thermocouple -200.0...400.0 °C NTC -60.0...150.0 °C For 0/4 - 20mA, 0 - 150mV, 0/1 - 5V, 0 - 10V, 0 - 550ohm, 0 - 10kohm: -32768...32767 (decimal point can be adjusted between 1. and 3. digits) |
Accuracy | ±0.1% or ±2 °C (for B type thermocouple) ±0.1% or ±0.5 °C (for E, J, K, N, T, U type thermocouple, Pt-100 resistance thermometer, NTC probe) ±0.1% or ±1.5 °C (for L type thermocouple) ±0.1% or ±1 °C (for R and S type thermocouple) ±0.1% or ±1 digit (for 0/4 - 20mA, 0/1 - 5V, 0 - 10V) ±0.1% or ±20μV (for 0 - 150mV) ±0.2% or ±0.1ohm (for 0 - 550ohm) ±0.5% or ±10ohm (for 0 - 10kohm) |
Line Resistance | For thermocouple, Pt-100, NTC, mV, V, ohm Ri > 100kohm For mA Ri = 50ohm |
Output | |
Control/Alarm 3 Output | Relay: 250V AC, 2A (for resistive load), NO+NC |
Alarm 1 Output | Relay: 250V AC, 2A (for resistive load), NO+NC |
Alarm 2 Output | Relay: 250V AC, 2A (for resistive load), NO |
SSR Output | Max. 40 mA, 0 - 12V, short-circuit protection |
mA Output | 0-20mA or 4-20mA, max. load resistance is 750ohm |
V Output | Max. 30mA, 0-10V DC, short-circuit protection |
Life Expectancy | Mechanical 10.000.000 operations (under no load), Electrical 200.000 operations (2A at 250V AC, resistive load) |
Housing | |
Mounting Method | Panel mounting |
Dimensions | G96xY96xD81 mm |
Weight | Approx. 400g (after packaging) |
Enclosure Material | Self extinguishing plastics |