Phase failure (loss phase) protection
Phase sequence protection
Adjustable voltage / asymmetry protection
Over voltage and/or low voltage protection
PTC protection
Contact output for system control (OUT)
Rail mounted, screw-terminal connections
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0 ...+50 ºC / -25...+70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | IP20, According to EN 60529 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 125-410V AC (Phase-Neutral), 125-500V AC (Phase-Phase) +10% -10% |
Operating Frequency | 45-65Hz |
Power Consumption | Max. 10VA |
External Connections | Screw-terminal connections |
Reset Time | Max. 0.01s |
Outputs | |
Control Output (OUT) | 250V AC, 10A (for resistive load), NO+NC |
Life Expectancy | Mechanical 10.000.000 operations (under no load), Electrical 50.000 operations (10A at 250V AC, resistive load) |
Control Output State | Out LED control output (OUT) lits when device is powered |
Housing | |
Mounting Method | TH35 rail mounting |
Dimensions | W18xH84xD62 mm |
Weight | Approx. 90g (after packaging) |
Enclosure Material | Self extinguishing plastics |