Selectable On-Off or time proportional control
Fe-Const thermocouple or Pt100 input
Adjustable proportional band
Suitable for 8-pins octal connector or plug-in terminal connection
In the case of sensor failure, control output will be disable
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C |
Protection Degree | According to EN 60529 Front panel: IP60, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230V AC +%10 -%20 or 10-30V DC/ 8-24V AC |
Power Consumption | 6VA |
External Connections | 8 pin octal connector or plug-in terminals |
Scale | For Fe-Const (J) thermocouple and Pt-100 resistance thermometer 0...400 °C For Fe-Const (J) thermocouple 0...300 °C / for Fe-Const (J) thermocouple için 0...200 °C |
Sensitivity | 1 ºC |
Accuracy | ±4% (of full scale) |
Outputs | |
Control Output | Relay: 250V AC, 3A (for resistive load), NO+NC or 10V DC 10mA logic output |
Life Expectancy | Mechanical 30.000.000 operations (under no load), Electrical 300.000 operations (3A at 250V AC, resistive load) |
Control Output State | When the control output is energized, OUT LED lits |
Control | |
Control Type | Single-set point control |
Control Algorithm | On-Off (Xp=0) or time proportional control |
Proportional Band | 5% (adjustable from the device) |
Hysteresis | 3 ºC (for On-Off control) |
Housing | |
Mounting Method | Panel mounting |
Dimensions | W48xH48xD82 mm |
Weight | Approx. 170g (after packaging) |
Enclosure Material | Self extinguishing plastics |