J type thermocouple input
Offset feature for input
C1 relay out for temperature control
When C1 output configuration is selected for cooling, compressor delay time can be entered
Selectable heating/cooling control
In case of sensor failure, relay state can be configured as On or Off
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel: IP62, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230V AC +%10 -%50 50/60Hz veya 10-30V DC / 8-24V AC |
Power Consumption | Power connector; 2.5mm² screw-terminal, Signal connector, 1,5mm² screw-terminal conenction |
External Connections | Screw-terminals |
Scale | Fe-Const (J) thermocouple -30...400 °C, NTC probe -25.0...110.0 °C |
Accuracy | ± 1% (of full scale) ± 1 digit |
Line Resistance | Max. 100ohm |
Indicator | 4 digits, 12.5mm, 7 segment red LED |
Output | |
C1 Output | 8A model: 250V AC, 8A (for resistive load), NO+NC control output |
Life Expectancy | 8A model: Mechanical 30.000.000 operations (under no load), Electrical 300.000 operations (8A at 250V AC, resistive load) |
Control | |
Control Type | Single-setpoint control |
Control Algorithm | On-Off |
A/D converter | 12 bit |
Sampling Time | 100ms |
Hysteresis | Adjustable between 0.1 and 5.0 °C |
Housing | |
Mounting Method | Panel mounting |
Dimensions | W77xH35xD61 mm |
Weight | Approx. 215g (after packaging) |
Enclosure Material | Self extinguishing plastics |