ET5011
  • PT100 input

  • PID control function with accurate self-tuning

  • Soft-Start function

  • Offset feature for input

  • C1 relay out for temperature control

  • Selectable heating/cooling control

  • In case of sensor failure, manual control can be selected

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeAccording to EN 60529 Front panel: IP62, Rear panel: IP20
HeightMax. 2000m
Electrical Characteristics
Supply230V AC +%10 -%20 50/60Hz or 10-30V DC / 8-24V AC
Power Consumption5VA
External ConnectionsScrew-terminals
ScalePt-100 resistance thermometer -200...600 °C
Pt-100 resistance thermometer -99.9...300.0 °C
Accuracy±0.5% (of full scale) ±1 digit
Line ResistanceMax. 100ohm
Output
C1 Output5A model: 250V AC, 5A (for resistive load), NO control output
8A model: 250V AC, 8A (for resistive load), NO+NC control output
16A model: 250V AC, 16A (for resistive load), NO control output
Life Expectancy5A model: Mechanical 5.000.000 operations (under no load), Electrical 100.000 operations (5A at 250V AC, resistive load)
8A model: Mechanical 30.000.000 operations (under no load), Electrical 300.000 operations (8A at 250V AC, resistive load)
16A model: Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (16A at 250V AC, resistive load)
Control
Control TypeSingle-setpoint control
Control AlgorithmOn-Off, P, PI, PD, PID (selectable)
A/D Converter12 bit
Sampling Time100ms
Proportional BandAdjustable between 0.0% and 100.0%. If Pb=0%, On-Off control is selected
Control PeriodAdjustable between 1 and 250s
HysteresisAdjustable between 1 and 50 °C/F
Output PowerThe ratio of power at a set point can be adjusted between 0% and 100%
Housing
Mounting MethodTH35 rail mounting
DimensionsW54xH94xD68 mm
WeightApprox. 190g (after packaging)
Enclosure MaterialSelf extinguishing plastics
Please choose your preferred language.
Switch to English