On-Off control
Relay output for cooling or heating control
Relay output for Alarm
Single NTC probe input
Offset value can be entered for NTC probe
In the case of probe failure, output state can be selected as On/Off or periodical running
Upper and lower limits of the setpoint can be adjusted
Upper and lower alarm limits can be adjusted depending on the set point value
Temperature unit can be selected as °C or °F
Communication feature via RS485 ModBus protocol(order option)
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel: IP65, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230V AC +%10 -%20 50/60Hz or 10-30V DC / 8-24V AC |
Power Consumption | 5VA |
External Connections | Screw-terminals |
Scale | -60.0...150.0 °C |
Sensitivity | 0.1°C (selectable 0.1 ºC or 1 ºC) |
Accuracy | ± 1% (of full scale) |
Output | |
Relay | 250V AC, 8A (for resistive load), NO+NC 1/2hp 240V AC (for inductive load) |
Life Expectancy | Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load) |
Control | |
Control Type | Single set-point and alarm control |
Control Algorithm | On-Off |
Hysteresis | Adjustable between 1 and 20.0 °C |
Housing | |
Mounting Method | TH35 rail mounting |
Dimensions | W54xH94xD68 mm |
Weight | Approx. 190g (after packaging) |
Enclosure Material | Self extinguishing plastics |